Nominal
capacity at 10'K
(i.e. return line 0°C above outlet)
(i.e. outlet 10'K above house supply) | | 50kW | | 85kW | | 120kW | | 200kW | |
Administrative Data | | | | | | | | | |
CAD
assembly dwg no. | |
MA503 | | MA503 | | MA503 | |
MA378 | |
ATC new model name | |
XF050 | |
XF085 | |
XF120 | |
XF200 | |
Enclosure
type | |
XF050 | |
XF050 | |
XF050 | | W24 | |
| | | | | | | | | |
Physical attributes | | | | | | | | | |
Physical dimensions(mm) | |
L1100 x
W750 x H1060mm | |
L1100 x
W750 x H1060mm | |
L1100 x
W750 x H1060mm | |
D1000 x
W1180 x H1733mm | |
Construction | | Sheet steel gauge 1.5mm | | Sheet steel gauge 1.5mm | | Sheet steel gauge 1.5mm | | Sheet steel gauge 1.5mm | |
| | Epoxy polyester powder coat | | Epoxy polyester powder coat | | Epoxy polyester powder coat | | Epoxy polyester powder coat | |
Mounting
type | |
Skids | |
Skids | |
Skids | |
Folded
steel feet, four corners | |
Acceptable
environment | |
Indoors
or outdoors sheltered | |
Indoors
or outdoors sheltered | |
Indoors
or outdoors sheltered | |
Indoors
or outdoors sheltered | |
Dry
weight | | 80kg | |
80kg | | 100kg | | 150kg | |
Wet
weight | | 130kg | | 130kg | | 210kg | | 330kg | |
Noise level (dB(A)) | |
≤50dB(A)@1m | |
≤50dB(A)@1m | |
≤50dB(A)@1m | |
≤50dB(A)@1m | |
Toolless access | | No | | No | | No | | No | |
| | | | | | | | | |
Temperature control attributes | | | | | | | | | |
Technology | |
Water-to-water
heat exchanger | |
Water-to-water
heat exchanger | |
Water-to-water
heat exchanger | |
Water-to-water
heat exchanger | |
Control
method | |
House-water
throttling | |
House-water
throttling | |
House-water
throttling | |
House-water
throttling | |
Temperature
stability | |
±1°C | |
±1°C | |
±1°C | |
±1°C | |
Cooling
capacity with 'setpoint' 5°K above supply | | 25kW | | 42kW | | 60kW | | 100kW | |
Cooling
capacity with 'setpoint' 10°K above supply | | 50kW | | 85kW | | 120kW | | 200kW | |
Cooling
capacity with 'setpoint' 20°K above supply | | 100kW | | 170kW | | 240kW | | 400kW | |
Maximum
ambient | |
+40°C | |
+40°C | |
+40°C | |
+40°C | |
Design
flowrate | | 80L/min | |
120L/min | | 150L/min | | P300 | |
Temperature
range (standard) | |
+4°C to
70°C | |
+4°C to
70°C | |
+4°C to
70°C | |
+4°C to
70°C | |
Temperature
resolution | |
0.1°C | |
0.1°C | |
0.1°C | |
0.1°C | |
Maximum
THR (Total Heat Rejection) | | Applied load, plus power in | | Applied load, plus power in
| | Applied load, plus power in
| | Applied load, plus power in
| |
| | | | | | | | | |
Water circuit attributes | | | | | | | | | |
System volume (L) | | 50L | | 50L | | 110L | | 180L | |
Pump Options | | P40, P80, P120 | |
P80,
P120, P150 | |
P120,
P150 | |
P200,
P300 | |
Pressure
control (settable pressure relief valve) | |
Discharge
pressure choke | |
Discharge
pressure choke | |
Discharge
pressure choke | |
Discharge
pressure choke | |
Standard fittings | |
1-1/2"
BSPPF | |
1-1/2"
BSPPF | |
1-1/2"
BSPPF | |
1-1/2"
BSPPF | |
Standard chemical compatibility | |
Hexid
Fluid, Water, Propylene Glycol | |
Hexid
Fluid, Water, Propylene Glycol | |
Hexid
Fluid, Water, Propylene Glycol | |
Hexid
Fluid, Water, Propylene Glycol | |
| | | | | | | | | |
Electrical attributes | | | | | | | | | |
(90-264Vac,
1/2, 50-60Hz) U-spec | | - | | - | | - | | - | |
(230Vac,
1, 50Hz) 0-spec | |
Available | | - | | - | | - | |
(115Vac, 1, 60Hz) 1-spec | | - | | - | | - | | - | |
(208-220Vac, 1/2, 60Hz) 2-spec | |
Available | | - | | - | | - | |
(400Vac,
3, 50Hz) 3-spec | |
Available | |
Available | |
Available | | Available | |
(480Vac,
3,60Hz) 4-spec | |
Available | |
Available | |
Available | | Available | |
5-spec | | - | | - | | - | | - | |
(Switchable
208Vac, 1/2, 60Hz | 220Vac, 1/2, 60Hz | 230Vac, 1, 50Hz) 6-spec | | - | | - | | - | | - | |
(Switchable
115Vac, 1, 60Hz | 220Vac, 1/2, 60Hz | 230Vac, 1, 50Hz) 7-spec | | - | | - | | - | | - | |
(208Vac,
3, 60Hz) 8-spec | |
Available | |
Available | |
Available | | - | |
(208-230Vac, 1/2, 50/60Hz) 9-spec | | - | | - | | - | | - | |
Overcurrent
fault-cleared restart mode | |
Manual | |
Manual | |
Manual | |
Manual | |
| | | | | | | | | |
Safety
interlocks, protections, standards and indicators | | | | | | | | | |
1st party approvals | |
CE, UKCA | |
CE, UKCA | |
CE, UKCA | |
CE, UKCA | |
3rd party approvals | | UL-ready | | UL-ready | | UL-ready | | UL-ready | |
Empty
fluid reservoir alarm | |
Process
stop interlock | |
Process
stop interlock | |
Process
stop interlock | |
Process
stop interlock | |
Low
fluid flow alarm | |
Available | |
Available | |
Available | | Available | |
Process
water pressure alarm | |
Available | |
Available | |
Available | |
Available | |
Temperature out of range alarm | |
Standard | |
Standard | |
Standard | | Standard | |
Motor
thermal overload | |
No | | | |
No | | | |
Emergency
off | |
No | | | | No | | | |
Warranty
options | |
2 year
parts, 1 year labour
Enhanced warranty options | |
2 year
parts, 1 year labour
Enhanced warranty options | |
2 year
parts, 1 year labour
Enhanced warranty options | | | |
Interlock
restored, restart mode | | Manual | | | |
Automatic | | | |
| | | | | | | | | |
Options available | | | | | | | | | |
High
temperature pack; SA00003 | |
Available,
to +75°C | |
Available,
to +75°C | |
Available,
to +75°C | |
Available,
to +75°C | |
Non-return
solenoid valve pack; SA00008 | |
Available | |
Available | |
Available | |
Available | |
High
temperature water circuit w/o heater; SA00009 | | Available | | Available | | Available | | Available | |
Low flow
alarm (KT); SA00010 | |
Available | |
Available | |
Available | |
Available | |
Onboard
RS485 data protocol; SA00011 | | Available | | Available | | Available | | Available | |
Standard
VFC set; SA00012 | | Available | | Available | | Available | | Available | |
In-line
deionising cartridge and fittings; SA00013 | |
Available | |
Available | |
Available | |
Available | |
CPC
quick release connectors; SA00016 | |
Available | |
Available | |
Available | |
Available | |
Installation
kit; SA00017 | | Available | | Available | | Available | | Available | |
Flow
meter pack output to RS485; SA00025 | | Available | | Available | | Available | | Available | |
Seismic
mounts; SA00026 | | Available | | Available | | Available | | Available | |
In-line
UV decontamination; SA00027 | | Available | | Available | | Available | | Available | |
Qwikfoot
kit; SA00028 | | Available | | Available | | Available | | Available | |
Stainless
enclosure; SA00029 | | Available | | Available | | Available | | Available | |
De-branding
of standard model; SA00030 | | Available | | Available | | Available | | Available | |
External
manifold (2-way); SA00042 | | Available | | Available | | Available | | Available | |
External
manifold (3-way); SA00043 | | Available | | Available | | Available | | Available | |
External
manifold (4-way); SA00044 | | Available | | Available | | Available | | Available | |
External
manifold (5-way); SA00045 | | Available | | Available | | Available | | Available | |
External
manifold (6-way); SA00046 | | Available | | Available | | Available | | Available | |
External
manifold (7-way); SA00047 | | Available | | Available | | Available | | Available | |
External
manifold (8-way); SA00048 | | Available | | Available | | Available | | Available | |
External
manifold (9-way); SA00049 | | Available | | Available | | Available | | Available | |
External
manifold (10-way); SA00050 | | Available | | Available | | Available | | Available | |
Remote
stop-start; SA00051 | | Available | | Available | | Available | | Available | |
Auto
refill; SA00052 | | Available | | Available | | Available | | Available | |
Fluid
adapters; SA00053 | | Available
| | Available
| | Available
| | Available
| |
Pressure
sensor; SA00055 | | Available | | Available | | Available | | Available | |
Pressure
sensor to RS485; SA00056 | | Available | | Available | | Available | | Available | |
Conductivity
sensor; SA00057 | | Available | | Available | | Available | | Available | |
Conductivity
sensor to RS485; SA00058 | | Available | | Available | | Available | | Available | |
Inverter-driven
pump; SA00059 | | Available | | Available | | Available | | Available | |
| | | | | | | | | |