Nominal capacity @ ambient 10°K higher than liquid out.
At stated flowrate, 10°K rise through application.Coil takes out 10°K. | | 8kW | | 12kW | | 40kW | |
Administrative Data | | | | | | | |
CAD assembly dwg no. | | MA097 | | MA252 | | MA407 | |
ATC new model name | | A081003 | | A121703 | | A404043 | |
| | A081008 | | A121708 | | A408043 | |
| | A081009 | | A121709 | | A408049 | |
| | A081703 | | | | | |
| | A081708 | | | | | |
| | A081709 | | | | | |
| | | | | | | |
Physical attributes | | | | | | | |
Physical dimensions(mm) | | L775 x W510 x H850mm | | L775 x W510 x H850mm | | W1180 x D1180 x H1933mm | |
Construction | | Sheet steel gauge 1.5mm | | Sheet steel gauge 1.5mm | | Sheet steel gauge 1.5mm | |
| | Epoxy polyester powder coat | | Epoxy polyester powder coated | | Body covers in 1.2mm gauge | |
| | | | | | Floorstanding, no castors | |
| | | | | | 1.5mm CR4 MILD STEEL, | |
| | | | | | Leatherette Semi-Gloss paint | |
Mounting type | | Castors, 2 swivel, 2 braked | | Castors, 2 swivel, 2 braked | | Floorstanding, no castors | |
Acceptable environment | | Indoors or outdoors sheltered | | Indoors or outdoors sheltered | | Indoors or outdoors sheltered | |
Weight (kg) | | 100 | | 100 | | 500kg | |
Noise level (dB(A)@1m) | | ≤65 | | ≤65 | | ≤65 | |
Toolless access | | Top cover | | Top cover | | No | |
| | | | | | | |
Temperature control attributes | | | | | | | |
Technology | | Air blast | | Air blast | | Air blast | |
Control method | | None, continuous fan | | None, continuous fan | | None, continuous fan | |
Temperature stability | | Load & ambient dependent | | Load & ambient dependent | | Load & ambient dependent | |
Cooling capacity with 'setpoint' 5°K above ambient | | 4kW | | 6kW | | 20kW | |
Cooling capacity with 'setpoint' 10°K above ambient | | 8kW | | 12kW | | 40kW | |
Cooling capacity with 'setpoint' 20°K above ambient | | 16kW | | 24kW | | 80kW | |
Maximum ambient | | +40°C | | +40°C | | +40°C | |
Design flowrate | | 12L/min | | 18L/min | | 80L/min | |
Maximum THR (Total Heat Rejection) | | Applied load, plus power in | | Applied load, plus power in | | Applied load, plus power in | |
| | | | | | | |
Water circuit attributes | | | | | | | |
Maximum permissible return line temperature | | +60°C | | +60°C | | +60°C | |
System volume (L) | | 11 | | 11 | | 240 | |
Pump options | | P10, P17 | | P17 | | P40, P80 | |
Pressure relief | | Spring loaded PRV | | Spring loaded PRV | | Spring loaded PRV | |
Standard fittings | | 1/2" BSPPF | | 1/2" BSPPF | | 1/2" BSPPF | |
Standard chemical compatibility | | Tap water, water-glycol mix | | Tap water, water-glycol mix | | Tap water, water-glycol mix | |
| | | | | | | |
Electrical attributes | | | | | | | |
(24Vdc, +V, 0V, E) L-spec | | - | | - | | - | |
(90-264Vac, 1/2, 50-60Hz) U-spec | | - | | - | | - | |
(230Vac, 1, 50Hz) 0-spec | | - | | - | | - | |
(115Vac, 1, 60Hz) 1-spec | | - | | - | | - | |
(400Vac, 3, 50Hz) 3-spec | | Available | | Available | | Available | |
4-spec | | - | | - | | - | |
5-spec | | - | | - | | - | |
(Switchable 208Vac, 1/2, 60Hz | 220Vac, 1/2, 60Hz | 230Vac, 1, 50Hz) 6-spec | | - | | - | | - | |
(Switchable 115Vac, 1, 60Hz | 220Vac, 1/2, 60Hz | 230Vac, 1, 50Hz) 7-spec | | - | | - | | - | |
(208Vac, 3, 60Hz) 8-spec | | Available | | Available | | Available | |
(208-230Vac, 1/2, 50/60Hz) 9-spec | | Available | | Available | | Available | |
| | | | | | | |
Safety interlocks, protections, standards and indicators | | | | | | | |
1st party approvals | | CE, UKCA | | CE, UKCA | | CE, UKCA | |
3rd party approvals | | UL-ready | | UL-ready | | Not UL-ready | |
Empty fluid reservoir alarm | | Standard, process stop | | Standard, process stop | | Standard, process stop | |
Low fluid flow alarm | | Optional | | Optional | | Optional | |
Temperature out of range alarm | | Optional | | Optional | | Optional | |
Temperature display | | Optional | | Optional | | Optional | |
Motor thermal overload | | Standard | | Standard | | Standard | |
Cooling system | | Four 250mm axial fans UL-approved, IP55. | | Six 250mm axial fans, UL-approved, IP55. | | Rosenberg EC fan, top mounted, | |
| | Pair of PED-compliant coils. | | Trio of PED-compliant coils. | | AKFG 630 K.6IF A4, IP54 | |
Water system | | Fluid level switch | | Fluid level switch | | Fluid level switch | |
| | UL-approved fuse protected | | Pump motor UL-approved | | Pump, Calpeda, non-UL | |
| | Pump motor | | Pump motor thermal overload | | Protection against overvoltage, undervoltage, current imbalance, dry running leakage, closed valve operations | |
Overcurrent protection | | Standard, via GV2 breaker | | Standard, via GV2 breaker | | Standard | |
Overcurrent fault-cleared restart mode | | Manual restart | | Manual restart | | Manual | |
Interlock-restored restart mode | | Manual by default. | | Manual by default. | | Manual by default. | |
| | Specify automatic with 'A' suffix on model number | | Specify automatic with 'A' suffix on model number | | Specify automatic with 'A' suffix on model number | |
Emergency off | | Not present | | Not present | | Not present | |
Warranty options | | 2 year parts, 1 year labour | | 2 year parts, 1 year labour | | 2 year parts, 1 year labour | |
| | Enhanced warranty options | | Enhanced warranty options | | Enhanced warranty options | |
| | | | | | | |
Options available | | | | | | | |
Remote alarm/power-off; SA00001 | | Available | | Available | | Available | |
Low temperature pack; SA00002 | | - | | - | | - | |
High temperature pack; SA00003 | | Available, to +85°C | | Available, to +85°C | | Available, to +85°C | |
Water cooled KT; SA00004 | | - | | - | | - | |
Water cooled K1; SA00005 | | - | | - | | - | |
Water cooled K4/K6/K9/K12; SA00006 | | - | | - | | - | |
Water cooled K3; SA00007 | | - | | - | | - | |
Non-return solenoid pack; SA00008 | | Available | | Available | | Available | |
High temperature water circuit w/o heater; SA00009 | | Available | | Available | | Available | |
Low flow alarm (KT); SA00010 | | Available | | Available | | Available | |
Onboard RS485 data protocol; SA00011 | | Available | | Available | | Available | |
Standard VFC set; SA00012 | | Available | | Available | | Available | |
In-line Deionising cartridge and fittings; SA00013 | | - | | - | | - | |
Stainless non-return solenoid valve; SA00014 | | Available | | Available | | Available | |
Castors to replace rubber feet; SA00015 | | - | | - | | - | |
CPC quick release connectors; SA00016 | | Available | | Available | | Available | |
Installation kit; SA00017 | | Available | | Available | | Available | |
Stainless steel pump and fittings; SA00018 | | Available | | Available | | Available | |
KT filter kit; SA000019 | | - | | - | | - | |
Mod for outdoor use; SA00020 | | Available | | Available | | Available | |
Particulate filter; SA00021 | | Available | | Available | | Available | |
Flow meter pack; SA00022 | | Available | | Available | | Available | |
Fan speed control (on/off); SA00023 | | Available, stability to ±2°C | | Available, stability to ±2°C | | Available, stability to ±2°C | |
Fan speed control (proportional); SA00024 | | Available, stability to ±0.5°C | | Available, stability to ±0.5°C | | Available, stability to ±0.5°C | |
Flow meter pack output to RS485; SA00025 | | Available | | Available | | Available | |
Seismic mounts; SA00026 | | Available | | Available | | Available | |
In-line UV decontamination; SA00027 | | Available | | Available | | Available | |
Qwikfoot kit; SA00028 | | Available | | Available | | Available | |
Stainless enclosure; SA00029 | | Available | | Available | | Available | |
De-branding of standard model; SA00030 | | Available | | Available | | Available | |
High ambient fans; SA00031 | | Available | | Available | | Available | |
Internal manifold (2-way); SA00032 | | Available | | Available | | Available | |
Internal manifold (3-way); SA00033 | | Available | | Available | | Available | |
Internal manifold (4-way); SA00034 | | - | | - | | - | |
Internal manifold (5-way); SA00035 | | - | | - | | - | |
Internal manifold (6-way); SA00036 | | - | | - | | - | |
Internal manifold (7-way); SA00037 | | - | | - | | - | |
Internal manifold (8-way); SA00038 | | - | | - | | - | |
Internal manifold (9-way); SA00039 | | - | | - | | - | |
Internal manifold (10-way); SA00040 | | - | | - | | - | |
Frost protection; SA00041 | | Available | | Available | | Available | |
External manifold (2-way); SA00042 | | Available | | Available | | Available | |
External manifold (3-way); SA00043 | | Available | | Available | | Available | |
External manifold (4-way); SA00044 | | Available | | Available | | Available | |
External manifold (5-way); SA00045 | | Available | | Available | | Available | |
External manifold (6-way); SA00046 | | Available | | Available | | Available | |
External manifold (7-way); SA00047 | | Available | | Available | | Available | |
External manifold (8-way); SA00048 | | Available | | Available | | Available | |
External manifold (9-way); SA00049 | | Available | | Available | | Available | |
External manifold (10-way); SA00050 | | Available | | Available | | Available | |
Remote stop-start; SA00051 | | Available | | Available | | Available | |
Auto refill; SA00052 | | Available | | Available | | Available | |
Fluid adapters; SA00053 | | Available | | Available | | Available | |
Extra Close Control; SA00054 | | - | | - | | - | |
Pressure sensor; SA00055 | | Available | | Available | | Available | |
Pressure sensor to RS485; SA00056 | | Available | | Available | | Available | |
Conductivity sensor; SA00057 | | Available | | Available | | Available | |
Conductivity sensor to RS485; SA00058 | | Available | | Available | | Available | |
Inverter-driven pump; SA00059 | | Available | | Available | | Available | |
| | | | | | | |